Model 1250-LTC
The Model 1250-LTC provides critical LTC Maintenance Data to assist in making informed decisions, while continuing to provide highly accurate local and remote indication of load tap changer position.
Applications
- Transformer Load Tap Changer Position
- Works in virtually all transformer LTC's
- Single Phase Voltage Regulator Position
- Provides absolute position feedback
- Tap Change Displacement (position variation, 0.1 degree resolution)
- Total Operations Count
- Number of Tap Changes “up to” or “down to” each Tap
- Number of Consecutive Tap Changes in one Direction
- Number of Days Since First or Last Change to Highest and Lowest Tap (Draghands)
- Number of Days Since Passing Through Neutral
- “Unstable Signal” and loss of signal detection
- Momentary Relay Acknowledgement at Each Tap Change
- High Tap and Low Tap Alarm Limits
Features
- Interfaces with PLC’s and PC-Based SCADA systems
- Elapsed Time Clock
- Full Duplex RS-232 Serial Communication or Addressable RS-485 Multi-Drop Communication
- Programmable via the Serial Port
- 2ea, Form A Dry Contact Relays
- Proportional Stepped Analog Output
- ASCII or MODBUS Protocols
- Highly Visible 5 Digit LED Display
- Small size fi ts in 1/8 DIN panel cut-out
Benefits
- Proven Reliability – many in Utility & Industrial operations for over 20 years
- Maintenance Free
- Can be retrofi ted to older LTC’s with existing synchros
- Easy Installation and Programming
- Flexible Communication Options
Specifications
| GENERAL |
| Input Signal |
Synchro (5 wire) 90V maximum |
| Resolution |
+/-0.001% of full scale or 6 arc minutes |
| Accuracy |
+/-0.02% of full scale maximum (.01%
typical) |
| Temperature Drift |
+/- 0.01% per °C |
| Operating Temperature |
0° to 55° C (standard) |
| Humidity |
10% - 90% non condensing |
| Weight |
24 ounces |
| Voltage |
117/234 +/- 10% |
| Frequency |
47 - 63 Hz |
| Load |
8 Watts, maximum |
| DISPLAY |
| Type |
5-digit LED |
| Digit Height |
0.56 inch (14.2 mm) |
| Viewing distance |
23 feet |
| Decimal point |
Field programmable (scaled modes only) |
| OPTIONAL
ANALOG OUTPUT |
| Outputs |
+/- 1 mA, 0-1mA, 0-2mA, 4-20mA (requires
external loop power) |
| Compliance |
10 Volts (0-1mA, +/-1mA, 0-2mA)
500 Ohms (4-20mA)
|
| Non-Linearity |
+/- 0.1% of full scale |
| Resolution |
12 bits (+/- 0.025% of full scale) |
| OPTIONAL
HI/LO RELAYS |
| Contact Rating |
3A @ 125/250 VAC (resistive), 30 VDC |
Ordering Information
| 1250B-U-W-X-Y-ZZZ = options, see below |
| OPTIONS |
| U = Output Options |
0 (0-1 mA) 2 (0-2 mA) 1 (±1 mA) 4 (4-20 mA) |
| W = Control |
R - Hi/Low Relay Limits |
| X = Input Option |
I - Input Isolation |
| Y = Comm. Options |
S - RS-232 M RS-485 MODBUS PB Parallel Data (BCD) |
| ZZZ = Line Voltage |
120 (120 VAC) or 240 (240 VAC) |
PDF Downloads
Datasheet
Manual
Application Bulletin